Secure Computing SG550 Dokumentacja Strona 23: DC Power

/ 64
Spis treści
Connecting Power
�
23
Installing and Connecting the Device
3.
Use a grounding cable to connect the device to earth ground, and do the
following:
a.
Verify that a licensed electrician has attached an appropriate
grounding-cable lug to the grounding cable.
b.
Connect one end of the grounding cable to a proper earth ground, such as
the rack in which the device is installed.
c.
Connect the other end of the grounding cable to the two-hole grounding lug
at the rear of an SSG 500-series device.
Figure 10: AC Grounding
4.
For each power supply unit (PSU), do the following:
a.
Insert the appliance-coupler end of a power cord into the appliance inlet on
the power-supply faceplate.
b.
Insert the plug into an AC power-source receptacle.
5.
Verify that the power cord does not block access to device components or
drape where people can trip on it.

DC Power

Each DC PSU has a single DC input (–48 VDC and return) that requires a dedicated
25 A (–48 VDC) circuit breaker.
Most sites distribute DC power through a main conduit that leads to frame-mounted
DC power distribution panels, one of which might be located at the top of the rack
that houses the router. A pair of cables (one input and one return) connects each set
of terminal studs to the power distribution panel.
Grounding lugs
Washer
CAUTION:
If your device includes an optional redundant DC PSU, connect each of
the two power supplies to different input-power sources. Failure to do so makes
the device susceptible to total power failure if one of the power supplies fails.

Plik PDF · ·

Drukuj

Drukuj dokument

Dzielenie się

Pytania o Secure Computing SG550

Nie ma jeszcze pytań o tę instrukcję. Zadaj pierwsze.

Zadaj pytanie

Odpowiadamy na podstawie instrukcji i wskazujemy stronę. Pytanie pojawi się w serwisie po sprawdzeniu.

Wszystkie pytania i odpowiedzi ›

Powiązane produkty i podręczniki dla Bramy / kontrolery Secure Computing SG550